Inspection History Details
Inspection Status: Approved
Inspection History: COMPL - INITIAL INSPECTION
Case Number - T08FR01466
Inspection Description - COMPL - INITIAL INSPECTION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/27/2008 | COMPL - INITIAL INSPECTION | Approved | ||
06/09/2008 | COMPL - INITIAL INSPECTION | Approved | Maintenance of fire protection systems 1) three 165 degree standard spray sprinklers need to be replaced in the spare head box 2) The storage of insulation shall not block access to the sprinkler inspectors test valve 3) Storage in the middle warehouse shall be lowered so as not to block sprinkler coverage |