Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR01459
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.10/08/08. | |
06/06/2008 | INSP - FULL | Violation | 1.) TFC 904.5.1 COMMERCIAL HOOD SYSTEM HAS NO CURRENT INSPECTION TAG. EXTINGUISHING SYSTEM MUST BE INSPECTED EVERY 6 MOS. | |
06/06/2008 | INSP - FULL | Violation | 2.) TFC 906.2 THE "K" CLASS PORTABLE FIRE EXTINGUISHER IN THE KITCHEN MUST BE TESTED AND INSPECTED ANNUALY. THERE IS NO CURRENT INSPECTION TAG ATTACHED TO THE EXTINGUISHER. | |
06/06/2008 | INSP - FULL | Violation | 3.) TFC 3003.5.3 TWO CO2 CYLINDERS IN THE BACK ROOM NEED TO BE KEPT SECURED TO PREVENT FALLING CAUSED BE CONTACT, VIBRATION OR SEISMIC ACTIVITY. |