Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2008 | INSP - FULL | Approved | All noted Tucson Fire Code violations have been corrected. | |
| 06/06/2008 | INSP - FULL | Correction Required | 901.6 Fire protection system maintenance 1) The inspectors test valve shall have an identification sign 2) The fire department connection shall have signage "Sprinkler System Connection" 3) The fire department connection shall be cleaned of all debris and backflushed if necessary 4) The spare head box shall have the correct wrench for changing sprinkler heads 5) Verticle sidewall sprinklers shall be placed in the head box 6) The painted sprinkler head above the entry to the west locker rooms shall be changed out 7) The sprinkler head in the maintenance shop, blocked by the light shall be unobstructed 8) An area in the maintenance shop has sprinklers that exceed the allowable distance for coverage 9) The snack bar soffitt shall have sprinkler protection added to the underside for correct coverage 10) Restroom entries have sprinklers that exceed the allowable distance off walls 11) Replace the missing sprinkler head above the office in the storeroom 12) The sprinkler riser control valve shall be secured with a lock and chain |