Case: T08FR01449

Parcel: 12110005D


Addresses:

4780 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01449

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.06/24/08
06/05/2008 INSP - FULL Violation 1.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT ABOVE FRONT EXIT DOOR IS NOT FUNCTIONING. THE EMERGENCY ILLUMINATION UNIT MUST BE SERVICED/REPAIRED.
06/05/2008 INSP - FULL Violation 2.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT ON NORTH WALL OF FOOD BUFFET AREA NEEDS TO BE SERVICED/REPAIRED TO PROVIDE REQUIRED EMERGENCY ILLUMINATION.
06/05/2008 INSP - FULL Violation 3.) TFC 1003.6 THE REAR EXIT DOOR FROM THE KITCHEN IS OBSTRUCTED BY EMPTY CARDBOARD BOXES. THIS DOOR MUST BE UNOBSTRUCTED AT ALL TIMES.
06/05/2008 INSP - FULL Violation 4.) TFC 904.11.6.3 THERE IS A BUILD UP GREASE ABOVE THE FILTERS IN THE DUCT WORK. THE GREASE MUST BE CLEANED OUT OF DUCT SYSTEM ALL THE WAY UP TO THE ROOF.
06/05/2008 INSP - FULL Violation 5.) TFC 901.6 THE SPRINKLER HEADS INSIDE THE FREEZER UNITS NEED TO HAVE FOAM INSULATION SPRAYED INTO OPEN AREA AROUND HEADS.
06/05/2008 INSP - FULL Violation 6.) TFC 904.11.6.1 THE COMMERCIAL HOOD VENTALITION SYSTEM NEEDS TO BE SERVICED OR REPAIRED SO THAT GREASE FILTER PANELS STAY DOWN IN THE PROPER POSITION WHEN THE VENTILATION FAN IS OPERATING.