Case: T08FR01444

Parcel: 12704245A


Addresses:

5039 E 5TH ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01444

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/01/2009 INSP - FULL Approved ALL NOTED TFC VIOLATONS HAVE BEEN CORRECTED.
NOTE: THE HOOD SYSTEM WAS UPGRADED TO UL 300 WITH A PERMIT AND APPROVED BY SYSTEM DESIGN.
06/04/2008 INSP - FULL Violation 1.) TFC 1011.1 EXITS AND EXIT ACCESS DOORS SHALL BE MARKED BY AN APPROVED EXIT SIGN. THE MAIN EXIT DOOR NEEDS AN APPROVED, ILLUMINATED EXIT SIGN.
06/04/2008 INSP - FULL Violation 2.) TFC 605.4 THE CUBE ELECTRICAL ADAPTER BY THE T.V. AT THE MAIN ENTRANCE NEEDS TO BE REPLACED WITH AN APPROVED, UL LISTED, FUSED POWER STRIP.
06/04/2008 INSP - FULL Violation 3.) TFC 605.4 THE MULTI-PLUG ADAPTER UNDER THE FISH TANK MUST BE REMOVED.
06/04/2008 INSP - FULL Violation 4.) TFC 1003.6 THE EMERGENCY EXIT IN DINING AREA MUST NOT BE BLOCKED. DINING BOOTH AND CHAIRS MUST BE MOVED TO PREVENT OBSTRUCTING THE EXIT DOOR.
06/04/2008 INSP - FULL Violation 5.) TFC 1006.1 THE EMERGENCY ILLUMINATION UNIT NEEDS TO BE REPAIRED TO PROVIDE REQUIRED EMERGENCY ILLUMINATION IN CASE OF POWER OUTAGE.
06/04/2008 INSP - FULL Violation 6.) TFC 605.4 THE CUBE ELECTRICAL ADAPTER IN KITCHEM ABOVE THE FREZZER NEEDS TO BE REPLACED WITH AN APPROVED, UL LISTED, FUSED POWER STRIP.
06/04/2008 INSP - FULL Violation 7.) TFC 904.11.6.3 THE KITCHEN HOOD SYSTEM MUST BE CLEANED TO REMOVE GREASE. THE DUCT SYSTEM MUST BE CLEANED ALL THE WAY UP TO THE ROOF. THIS HOOD SYSTEM MUST BE CLEANED AS NECESSARY TO PREVENT THE ACCUMULATION OF GREASE.
06/04/2008 INSP - FULL Violation 8.) TFC 904.5.1 THE KITCHEN HOOD EXTINGUISHMENT SYSTEM NEEDS TO HAVE AN UP TO DATE 6 MO. INSPECTION AND TAGGED.
06/04/2008 INSP - FULL Violation 9.) TFC 904.11.5 A PORTABLE, CLASS "K" RATED, FIRE EXTINGUISHER SHALL BE PROVIDED FOR KITCHEN COOKING EQUIPMENT.