Case: T08FR01442

Parcel: 11301146Z


Addresses:

3699 N CAMPBELL AV


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR01442

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2008 VIOL - FIRE PROTECTION SYSTEMS Approved
06/04/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall
be selected, installed and maintained in accordance with this
section and NFPA 10.
1) Have fire extinquisher in kitchen serviced.
06/04/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.4 Extinguishing system service. Automatic
fire-extinguishing systems shall be serviced at least
every 6 months and after activation of the system.
Inspection shall be by qualified individuals, and a certificate
of inspection shall be forwarded to the fire code official
upon completion.
1) Hood fire extinquishing system needs to be serviced.
2) Repair the manual pull station.
06/04/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 903.3 Installation requirements. Automatic sprinkler systems
shall be designed and installed in accordance with Sections
903.3.1 through 903.3.7.
1) Remove large shelf in storage area that is obstructing the sprinkler head.