Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR01437

Parcel: 10714376H


Addresses:

515 E GRANT RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR01437

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/04/2008 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.4 Bolt locks.
Manually operated flush bolts or surface bolts are not permitted.

_____ remove the two slide bolts from rear egress door

1008.1.8.5 Unlatching.
The unlatching of any door or leaf shall not require more than one operation.

_____ Remove the drop bar system from the rear egress door

1011.5.3 Power source.
Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code

_____ Fix, repair, and bring both exit signs into code compliance

1027.5 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the
premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027.

_____ Fix, repair, and bring the emergency lighting unit into code compliance









________________________________________________
(Joseph P. Longo, Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report.
(Building Representative)

______________________________
(Captain)

Full inspection done by Inspector Joseph P. Longo
Re-inspection scheduled on or after ___/___/___
Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions.
Thank you.

Re-inspection passed:

______________________
Joseph P. Longo