Inspection History Details
Inspection Status: Compliance
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2008 | INSP - FULL | Compliance | 1) Spare head box needs a wrench for 1/2" Central A sprinklers 2) All dust loaded sprinklers shall be cleaned 3) Sprinkler heads over tables 8-9-10 have bent deflectors and need to be changed out 4) lower storage in liquor closet no closer than 18" below a sprinkler deflector |