Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR01398
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/14/2008 | INSP - FULL | Approved | fire drill conducted | |
06/03/2008 | INSP - FULL | Violation | 1). Remove combustible trash in elevator room. IFC 315.2.3 2). Repair fire stopping in 5th floor electrical room and 4th floor 701.3 3), Sprinkler test required. Report shall be submitted to TFD. IDC 901.6 4). Fire alarm test shall be required. IFC 901.6 5). Fire drill required. Date shall be submitted on recheck date IFC 404 |