Case: T08FR01367

Parcel: 12407185A


Addresses:

721 E 12TH ST


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR01367

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
04/28/2009 VIOL - FIRE PROTECTION SYSTEMS Approved ANNUAL INSPECTION 2-9-2009, SHOWED NO DEFICIENCIES, PREVIOUS WERE CORRECTED.
05/30/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.6 Maintenance of fire protection equipment
1) The hydraulic calculation plates at the riser were painted over and shall be replaced
2) The control valves shall have identification plates affixed
3) The plastic pipe for the sump pump shall be removed fron sprinkler piping
4) The plexiglass roof in the jamming area shall be removed or sprinkler protection added to the under side. the addition of sprinklers to this area will require submittals and permits. Submittals shall be made within 30 days and work completed with in 60 days
5) Sprinkler protection shall be added to the small office restroom. submittals are also required.
6) Keys shall be available for removing the lock at the main riser so that an annual flow test can be performed on the water supply