Case: T08FR01363

Parcel: 13416223A


Addresses:

7285 E 22ND ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
06/16/2008 INSP - FULL Approved
05/30/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Emergency light by back exit not working.
TFC REFERENCE: 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
REQUIRED CORRECTION: Have qualified individual repair emergency lighting unit.

___2. PROBLEM: Exit signs in main dining area not lit.
TFC REFERENCE: 1011.2 Illumination. Exit signs shall be internally or externally illuminated.
REQUIRED CORRECTION: Have exit signs repaired by qualified individual.

___3. PROBLEM: Hood system needs cleaning especially the filters.
TFC REFERENCE: 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at
intervals necessary to prevent the accumulation of
grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records
shall be maintained on the premises.
REQUIRED CORRECTION: Have qualified professionals completely clean Hood system.

The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

__X_Approved

___Not Approved