Case: T08FR01356

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01356

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
11/13/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
THE PETITION OF APPEAL TO THE FIRE CHIEF FOR CARD SLIDE LOCK RELEASES ON O.R. HALLWAY (NORTH AND SOUTH) EXIT DOORS WAS APPROVED AND WERE INSTALLED.
09/26/2008 INSP - FULL Violation 1.) TFC 1011.4 EXIT SIGN IS NOT ILLUMINATED. WEST EXIT TO O.R.
05/29/2008 INSP - FULL Violation 2.) TFC 1008.1.8 EGRESS DOORS SHALL BE OPENABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR EFFORT.
A.) EAST EXIT DOORS OF 380'S O.R. HALLWAY LOCKED.
B.) SOUTHEAST EXIT DOORS OF 370'S O.R. HALLWAY LOCKED.
05/29/2008 INSP - FULL Violation 3.) TFC 703.1 THERE IS A HOLE CREATING A WALL PENETRATION IN A RATED CORRIDOR NEAR THE FLOOR OUTSIDE OF O.R. SUITE #385.
05/29/2008 INSP - FULL Violation 4.)TFC 605.6 OPEN WIRE SPLICES VISIBLE IN DOOR CLOSING MECHANISM ON TOP OF PACU WEST EXIT DOOR. A COVER PLATE NEEDS TO BE INSTALED.