Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR01356
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. THE PETITION OF APPEAL TO THE FIRE CHIEF FOR CARD SLIDE LOCK RELEASES ON O.R. HALLWAY (NORTH AND SOUTH) EXIT DOORS WAS APPROVED AND WERE INSTALLED. |
|
09/26/2008 | INSP - FULL | Violation | 1.) TFC 1011.4 EXIT SIGN IS NOT ILLUMINATED. WEST EXIT TO O.R. | |
05/29/2008 | INSP - FULL | Violation | 2.) TFC 1008.1.8 EGRESS DOORS SHALL BE OPENABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR EFFORT. A.) EAST EXIT DOORS OF 380'S O.R. HALLWAY LOCKED. B.) SOUTHEAST EXIT DOORS OF 370'S O.R. HALLWAY LOCKED. |
|
05/29/2008 | INSP - FULL | Violation | 3.) TFC 703.1 THERE IS A HOLE CREATING A WALL PENETRATION IN A RATED CORRIDOR NEAR THE FLOOR OUTSIDE OF O.R. SUITE #385. | |
05/29/2008 | INSP - FULL | Violation | 4.)TFC 605.6 OPEN WIRE SPLICES VISIBLE IN DOOR CLOSING MECHANISM ON TOP OF PACU WEST EXIT DOOR. A COVER PLATE NEEDS TO BE INSTALED. |