Case: T08FR01325

Parcel: 12112001B


Addresses:

5455 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01325

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/12/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.06/11/08
05/28/2008 INSP - FULL Violation 1.) TFC 315.2.1 STORAGE ON TOP OF COOLER IN STOCKROOM NEEDS TO BE ARRANGED TO MAINTAIN 18" OF CLEARANCE BELOW THE SPRINKLER HEADS.
05/28/2008 INSP - FULL Violation 2.) TFC 605.3 A WORKING SPACE OF NOT LESS THAN 30" SHALL BE PROVIDED IN FRONT OF ELECTRICAL SERVICE EQUIPMENT. THE MERCHANDISE STACKED IN FRONT OF ELECTRICAL PANELS IN THE BACK ROOM NEEDS TO MOVED TO PROVIDE 30" WORKING SPACE.