Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/12/2008 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.06/11/08 |
| 05/27/2008 |
INSP - FULL |
|
Violation |
1.) TFC 605.6 ELECTRICAL OUTLET ON THE WALL NEAR MEN'S BATHROOM NEEDS A COVER PLATE INSTALLED. |
| 05/27/2008 |
INSP - FULL |
|
Violation |
2.) TFC 315.2.1 STORAGE IN STOCK ROOM AREA NEEDS TO BE ARRANGED TO MAINTAIN 2 FEET CLEARANCE BETWEEN STORAGE AND THE CEILING. |
| 05/27/2008 |
INSP - FULL |
|
Violation |
3.) TFC 605.6 JUNCTION BOX IN CEILING ABOVE THE STOCK ROOM HAS AN OPEN ELECTRICAL WIRE SPLICE. THE JUNCTION BOX NEEDS A COVER PLATE INSTALLED. |
| 05/27/2008 |
INSP - FULL |
|
Violation |
4.) TFC 605.1 THE ELECTRICAL CORD FOR THE SHREDDER NEEDS TO HAVE THE PLUG INSTALLED IN AN APPROVED MANNER. |
| 05/27/2008 |
INSP - FULL |
|
Violation |
5.) TFC 605.6 THE ELECTRICAL JUNCTION BOX IN THE CEILING NEAR THE REAR EXIT NEEDS A COVER PLATE INSTALLLED. |
| 05/27/2008 |
INSP - FULL |
|
Violation |
6.) TFC 315.2.2 COMBUSTIBLE NATERIALS STORED UNDER EXIT STAIRS FROM THE OFFICE NEEDS TO BE REMOVED TO PREVENT EXIT ACCESS IN CASE OF FIRE. |