Case: T08FR01263

Parcel: 12213023A


Addresses:

4151 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/14/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.07/14/08
05/20/2008 INSP - FULL Violation 1.) TFC 315.2.1 STORAGE AND MERCHANDISE DISPLAYS THROUGHOUT THE BUILDING MUST BE ARRANGED TO MAINTAIN 2 FEET CLEARANCE FROM THE CEILING.
05/20/2008 INSP - FULL Violation 2.) TFC 906.2 FIRE EXTINGUISHERS THROUGHOUT THE PREMISES ARE PAST DUE FOR THE ANNUAL INSPECTION. ALL PORTABLE FIRE EXTINGUISHERS MUST HAVE A CURRENT INSPECTION TAG.
05/20/2008 INSP - FULL Violation 3.) TFC 605.5 ELECTRICAL EXTENSION CORDS ARE NOT ALLLOWED TO BE A SUBSTITUTE FOR PERMANENT WIRING. THE ORANGE EXTENSION CORD USED TO POWER THE REFRIGERATOR IS NOT PERMITTED TO BE USED.
05/20/2008 INSP - FULL Violation 4.) TFC 605.4 MULTI-PLUG CUBE ADAPTERS ARE NOT PERMITTED BY THE CURRENT FIRE CODE. THE TWO CUBE ADAPTERS BEING USED BEHIND THE SALES COUNTER NEED TO BE REPLACED WITH UL APPROVED PLUG STRIPS WITH OVER CURRENT PROTECTION.
05/20/2008 INSP - FULL Violation 5.) TFC 1003.6 ITEMS STORED NEAR EXIT DOOR IN NORTHWEST CORNER OF DISPLAY FLOOR ARE OBSTRUCTING EXIT ACCESS. THIS AREA MUST BE KEPT CLEAR AT ALL TIMES.
05/20/2008 INSP - FULL Violation 6.) TFC 703.1.1 THE HOLES IN THE CEILING ABOVE THE TABLE SAW IN THE WOODWORKING SHOP NEED TO BE COVERED TO PROVIDE REQUIRED FIRE BLOCKING AND DRAFT STOPPING.
05/20/2008 INSP - FULL Violation 7.) TFC 605.6 THE OPEN WIRE SPLICE VISIBLE IN THE HOLE IN CEILING ABOVE THE TABLE SAW NEEDS TO BE PROPERLY ENCLOSED IN A JUNCTION BOX.
05/20/2008 INSP - FULL Violation 8.) TFC 605.6 THE OPEN WIRE SPLICE ABOVE THE ENTRANCE TO THE WOODWORKING SHOP NEEDS TO BE ENCLOSED IN AN APPROVED JUNCTION BOX.
05/20/2008 INSP - FULL Violation 9.) TFC 1504.1 THE APPLICATION OF FLAMMABLE OR COMBUSTIBLE LIQUIDS BY MEANS OF SPRAY APPARATUS IN CONINUOUS OR INTERMITTENT PROCESSES SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTIONS 1503 AND 1504. SPRAY AREA BEING USED IS NOT APPROVED FOR FLAMMABLE OR COMBUSTIBLE LIQUIDS.
05/20/2008 INSP - FULL Violation TFC 111.1 WHENEVER THE FIRE CODE OFFICIAL FINDS ANY WORK REGULATED BY THE TUCSON FIRE CODE BEING PERFORMED IN A MANNER CONTRARY TO THE PROVISIONS OF THE CODE OR IN A DANGEROUS OR UNSAFE MANNER, THE FIRE CODE OFFICIAL IS AUTHORIZED TO ISSUE A STOP WORK ORDER.
STOP WORK ORDER: ALL SPRAYING OF FLAMMABLE LIQUIDS INSIDE OF BUILDING SHALL IMMEDIATELY CEASE.
05/20/2008 INSP - FULL Violation 10.) TFC 1405.3 STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS SHALL BE SEPARATED FROM STORAGE OF COMBUSTIBLE MATERIALS.
05/20/2008 INSP - FULL Violation 11.) TFC 1903.3 SAWMILLS, PLANING MILLS AND WOODWORKING PLANTS SHALL BE EQUIPPED WITH A WASTE REMOVAL SYSTEM THAT WILL COLLECT AND REMOVE SAWDUST AND SHAVINGS.