Case: T08FR01261

Parcel: 13339282B


Addresses:

15 S HARRISON RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
06/03/2008 INSP - FULL Approved
05/19/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1.PROBLEM: Main entrance with double key lock needs sign above door indicating that the door is to remain unlocked while building is occupied.
TFC REFERENCE: 1008.1.8.3.2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS
OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background.
REQUIRED CORRECTION: Have above indicated sign placed above door.

___2. PROBLEM: Brown extension cord leading to Icee sign.
TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. REQUIRED CORRECTION: Plug appliance directly into outlet or into an approved power strip with a GFI.

___3. PROBLEM: Fan motor in bathroom needs cover plate.
TFC REFERENCE: 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
REQUIRED CORRECTION: Have fan motor repaired and cover plate replaced.

___4. PROBLEM: Storage in front of electrical panel blocking access to panels.
TFC REFERENCE: 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated working space.
REQUIRED CORRECTION: Keep area around electrical panel clear so that access will not be hindered.

The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved