Case: T08FR01256

Parcel: 124190190


Addresses:

1655 E 18TH ST

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
05/16/2008 INSP - FULL Correction Required Suite 101 Fire extinguishers shall be serviced annually

Suite 107 Repair the open light socket in the short hallway

Suite 109 No hazards noted

Suite 112 a) Storage shall be no closer than 18 " below a sprinkler head. b)The fire extinguisher shall be serviced annualy c)Extention cords shall not be used in place of permanent wiring

Suite 115 a) Insulation is blocking the sprinkler spray pattern b)the fire extinguisher shall be serviced annualy ang hung c) the emergency lighting shall be repaired and in service

Suite 204 Remove the wiring from sprinkler piping

Suite 206 a) Add a sprinkler head inside of the curtain by the clean room b) Fire extinguisher shall be serviced annualy and accessable c) The flammable liquids cabinet shall be self closure and self latching

Suite 207 a) sprinkler protection shall be added to the rest room, the ceiling can be removed in place of b) Sprinklers shall be added to the under side of the shelving by yhe back door, or it coould be cut back to two feet.

Suite 208 a) fire extinguisher to be serviced annually and hung
b) provide a face plate for the electrical outlet

Suite 211/212 Fire extinguisher shall be services annualy and hung b) provide a cover for the electrical wall switch in 121

Suite 216/217 a) Extention cords shall not be used in place of permanent wiring b) The kitchen hood extinguishing system shall be serviced semi-annually

The following suites were locked or vacant 105,108, 110.,113,114,116,120,121,205,214, inspections were not done in there areas