Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR01237
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/01/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.07/01/08 | |
05/15/2008 | INSP - FULL | Violation | 1.) TFC 315.2.1 STORAGE ABOVE OFFICE NEEDS TO BE LOWERED OR REMOVED TO MAINTAIN 18" CLEARANCE BELOW CEILING AND SPRINKLER HEAD. | |
05/15/2008 | INSP - FULL | Violation | 2.) TFC 1003.6 EMPTY BOXES BEHIND REAR EXIT DOOR MUST BE REMOVED. THIS AREA MUST BE KEPT CLEAR AT ALL TIMES TO PREVENT BLOCKING EXIT DOOR AND EXIT DISCHARGE. | |
05/15/2008 | INSP - FULL | Violation | 3.) TFC 901.6 PAINTED SPRINKLER HEAD INSIDE FREEZER NEEDS TO BE REPLACED WITH AN UNPAINTED HEAD. |