Case: T08FR01233

Parcel: 105102430


Addresses:

605 E WETMORE RD


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T08FR01233

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/14/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3 Working space and clearance
A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space

_____ Move all storage and/or obstructions to maintain the code standards around the storage room electrical panels.





605.6 Unapproved conditions
Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers.

_____ Place all proper covers on all electrical outlets.