Case: T08FR01218

Parcel: 12710084B


Addresses:

1031 N WILMOT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01218

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/28/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
05/12/2008 INSP - FULL Violation 1.) TFC 906.5 PORTBLE FIRE EXTINGUISHERS SHALL BE LOCATED IN A CONSPICUOUS LOCATION WHERE THEY WILL BE READILY ACCESSIBLE AND IMMEDIATELY AVAILABLE FOR USE. THE FIRE EXTINGUISHER UNDER THE WORK BENCH NEEDS TO BE MOUNTED IN A CONSPOICUOUS LOCATION.
05/12/2008 INSP - FULL Violation 2.) TFC 906.2 PORTABLE FIRE EXTINGUISHERS NEED TO BE INSPECTED AND TAGGED ANNUALLY. BOTH EXTINGUISHERS NEED TO A CURRENT INSPECTION TAG.
05/12/2008 INSP - FULL Violation 3.) TFC 605.5 EXTENSION CORDS SHALL NOT BE A SUBSTITUTE FOR PERMANENT WIRING. THE EXTENSION CORD USED TO POWER SIGN IN THE FRONT WINDOW IS NOT PERMITTED.
05/12/2008 INSP - FULL Violation 4.) 1011.2 EXIT SIGNS SHALL BE INTERNALLY OR EXTERNALLY ILLUMINATED. THE EXIT SIGN ABOVE THE MAIN ENTRANCE AND BOTH EXIT SIGNS BEHIND THE SALES COUNTER ARE NOT ILLUMINATING.
05/12/2008 INSP - FULL Violation 5.) TFC 605.6 ELECTRICAL OUTLET BOX ON WALL BEHIND SALES COUNTER NEEDS TO HAVE A COVER PLATE INSTALLED.