Case: T08FR01177

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01177

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
07/24/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.07/24/08
05/08/2008 INSP - FULL Violation 1.) TFC 703.1.1 ONE BROKEN CEILING TILE AND ONE MISSING CEILING TILE IN KITCHEN DISHWAHSING AREA. BROKEN AND MISSING TILE NEED TO BE REPLACED.
05/08/2008 INSP - FULL Violation 2.) TFC 903.3.1 SPRINKLER HEAD ESCUTCHEON DOES NOT COVER ACCESS HOLE IN CEILING. KITCHEN OFFICES HALLWAY-NORTH SPRINKLER HEAD.
05/08/2008 INSP - FULL Violation 3.) TFC 1003.6 WEST EXIT OFF OF KITCHEN OFFICES HALLWAY HAS TABLES BLOCKING EXIT ACCESS. TABLES NEED TO BE REMOVED.
05/08/2008 INSP - FULL Violation 4.) TFC 1011.1 WEST EXIT OFF OF KITCHEN OFFICES HALLWAY NEEDS AN APPROVED EXIT SIGN INSTALLED ABOVE DOOR LEADING TO ACTUAL EXIT.
05/08/2008 INSP - FULL Violation 5.) TFC 903.3.1 MEN'S RESTROOM OFF OF KITCHEN OFFICES HALLWAY HAS TWO SPRINKLER HEADS WITH A GAP BETWEEN THE TOP OF THE ESCUTCHEON AND THE CEILING.
05/08/2008 INSP - FULL Violation 6.) TFC 703.1.1 FOOD SERVICES DIRECTOR'S OFFICE HAS HOLE IN CEILING ABOVE THE A/C UNIT.
05/08/2008 INSP - FULL Violation 7.) TFAC 703.1.1 FOOD SERVICES OFFICE OUTSIDE OF DIRECTOR'S OFFICE HAS HOLE IN CEILING ABOVE A/C UNIT.
05/08/2008 INSP - FULL Violation 8.) TFC 903.3.1 GAPS EXIST AROUND THE ESCUTCHEON AND ACCESS HOLE IN CEILING OF FOOD SERVICES OFFICE AREA AND ALSO IN CONFERENCE ROOM.
05/08/2008 INSP - FULL Violation 9.) TFC 605.6 ELECTRICAL BOX MOUNTED ON SUPPORT BEAM IN BASEMENT OF KITCHEN AREA BY WATER SOFTENER NEEDS A COVER PLATE.
05/08/2008 INSP - FULL Violation 10.) TFC 315.2.1 IN KITCHEN BASEMENT "EQUIPMENT STORAGE ROOM", STORAGE ON TOP OF SHELVES IN THE MIDDLE OF THE ROOM NEEDS TO BE REMOVED TO PREVENT OBSTRUCTING SPRINKLER COVERAGE.
05/08/2008 INSP - FULL Violation 11.) TFC 605.1 IN SUPERVISOR'S OFFICE OF PATIENT MEAL PREP AREA THERE IS ONE BROKEN AND ONE MISSING OUTLET COVER PLATE THAT NEED TO BE REPLACED.
05/08/2008 INSP - FULL Violation 12.) TFC 903.3.1.1 THE FRONT SPRINKLER HEAD IN WALK-IN FREEZER OF PATIENT PREP AREA NEEDS TO BE SEALED WITH FOAM INSULATION.
05/08/2008 INSP - FULL Violation 13.) TFC 703.1.1 IN OLD INFECTION CONTROL AREA AT END OF BATHROOM HALLWAY THERE IS A HOLE IN WALL BY DOOR THAT NEEDS TO BE SEALED.