Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/24/2008 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.07/24/08 |
| 05/08/2008 |
INSP - FULL |
|
Violation |
1.) TFC 703.1.1 ONE BROKEN CEILING TILE AND ONE MISSING CEILING TILE IN KITCHEN DISHWAHSING AREA. BROKEN AND MISSING TILE NEED TO BE REPLACED. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
2.) TFC 903.3.1 SPRINKLER HEAD ESCUTCHEON DOES NOT COVER ACCESS HOLE IN CEILING. KITCHEN OFFICES HALLWAY-NORTH SPRINKLER HEAD. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
3.) TFC 1003.6 WEST EXIT OFF OF KITCHEN OFFICES HALLWAY HAS TABLES BLOCKING EXIT ACCESS. TABLES NEED TO BE REMOVED. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
4.) TFC 1011.1 WEST EXIT OFF OF KITCHEN OFFICES HALLWAY NEEDS AN APPROVED EXIT SIGN INSTALLED ABOVE DOOR LEADING TO ACTUAL EXIT. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
5.) TFC 903.3.1 MEN'S RESTROOM OFF OF KITCHEN OFFICES HALLWAY HAS TWO SPRINKLER HEADS WITH A GAP BETWEEN THE TOP OF THE ESCUTCHEON AND THE CEILING. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
6.) TFC 703.1.1 FOOD SERVICES DIRECTOR'S OFFICE HAS HOLE IN CEILING ABOVE THE A/C UNIT. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
7.) TFAC 703.1.1 FOOD SERVICES OFFICE OUTSIDE OF DIRECTOR'S OFFICE HAS HOLE IN CEILING ABOVE A/C UNIT. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
8.) TFC 903.3.1 GAPS EXIST AROUND THE ESCUTCHEON AND ACCESS HOLE IN CEILING OF FOOD SERVICES OFFICE AREA AND ALSO IN CONFERENCE ROOM. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
9.) TFC 605.6 ELECTRICAL BOX MOUNTED ON SUPPORT BEAM IN BASEMENT OF KITCHEN AREA BY WATER SOFTENER NEEDS A COVER PLATE. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
10.) TFC 315.2.1 IN KITCHEN BASEMENT "EQUIPMENT STORAGE ROOM", STORAGE ON TOP OF SHELVES IN THE MIDDLE OF THE ROOM NEEDS TO BE REMOVED TO PREVENT OBSTRUCTING SPRINKLER COVERAGE. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
11.) TFC 605.1 IN SUPERVISOR'S OFFICE OF PATIENT MEAL PREP AREA THERE IS ONE BROKEN AND ONE MISSING OUTLET COVER PLATE THAT NEED TO BE REPLACED. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
12.) TFC 903.3.1.1 THE FRONT SPRINKLER HEAD IN WALK-IN FREEZER OF PATIENT PREP AREA NEEDS TO BE SEALED WITH FOAM INSULATION. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
13.) TFC 703.1.1 IN OLD INFECTION CONTROL AREA AT END OF BATHROOM HALLWAY THERE IS A HOLE IN WALL BY DOOR THAT NEEDS TO BE SEALED. |