Case: T08FR01164

Parcel: 105102430


Addresses:

575 E WETMORE RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR01164

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/08/2008 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.5 Unlatching.
The unlatching of any door or leaf shall not require more than one operation.

_____ Please remove any additional locking devices from the rear storage room panic hardware door.

1011.4 Internally illuminated exit signs.
Internally illuminated exit signs shall be listed and labeled and shall be installed in accordance with the manufacturer's instructions and Section 2702 of the International Building Code. Exit signs shall be illuminated at all times.

_____ Fix all Exit signs that are inoperative or that have non-working bulbs.

1027.5 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027.

_____ Repair/Fix the emergency lighting unit.



________________________________________________
(Joseph P. Longo, Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report.
(Building Representative)

______________________________
(Captain)

Full inspection done by Inspector Joseph P. Longo
Re-inspection scheduled on or after ___/___/___
Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions.