Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/21/2008 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. 05/21/08 |
| 05/08/2008 |
INSP - FULL |
|
Violation |
1.) TFC 605.6 ELECTRICAL EXTENSION CORDS ARE NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING. THE EXTENSION CORDS CURRENTLY USED BEHIND THE ICE MACHINE AND ALSO ONE USED FOR POWERING A RADIO AND ADDING MACHINE IN THE SERVICE AREA MUST BE REMOVED. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
2.) TFC 305.1 THE TRASH CAN IN THE BACK ROOM IS TOO CLOSE TO THE GAS WATER HEATER. THE FIRE CODE REQUIRES A SAFE CLEARANCE BETWEEN COMBUSTIBLE MATERIALS AND FLAME PRODUCING DEVICES. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
3.) TFC 3003.5.3 THE CO2 CYLINDER IN THE BACK ROOM NEEDS TO BE SECURED TO PREVENT FALLING CAUSED BY CONTACT, VIBRATION OR SEISMIC ACTIVITY. |
| 05/08/2008 |
INSP - FULL |
|
Violation |
4.) TFC 904.5.1 WET-CHEMICAL EXTINGUISHING SYSTEMS SHALL BE INSPECTED AND TESTED FOR PROPER OPERATION AT 6 MO. INTERVALS. |