Case Number - T08FR01161

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/21/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. 05/21/08
05/08/2008 INSP - FULL Violation 1.) TFC 605.6 ELECTRICAL EXTENSION CORDS ARE NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING. THE EXTENSION CORDS CURRENTLY USED BEHIND THE ICE MACHINE AND ALSO ONE USED FOR POWERING A RADIO AND ADDING MACHINE IN THE SERVICE AREA MUST BE REMOVED.
05/08/2008 INSP - FULL Violation 2.) TFC 305.1 THE TRASH CAN IN THE BACK ROOM IS TOO CLOSE TO THE GAS WATER HEATER. THE FIRE CODE REQUIRES A SAFE CLEARANCE BETWEEN COMBUSTIBLE MATERIALS AND FLAME PRODUCING DEVICES.
05/08/2008 INSP - FULL Violation 3.) TFC 3003.5.3 THE CO2 CYLINDER IN THE BACK ROOM NEEDS TO BE SECURED TO PREVENT FALLING CAUSED BY CONTACT, VIBRATION OR SEISMIC ACTIVITY.
05/08/2008 INSP - FULL Violation 4.) TFC 904.5.1 WET-CHEMICAL EXTINGUISHING SYSTEMS SHALL BE INSPECTED AND TESTED FOR PROPER OPERATION AT 6 MO. INTERVALS.