Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Case: T08FR01161

Parcel: 12112415A


Addresses:

5416 E PIMA ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
05/21/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. 05/21/08
05/08/2008 INSP - FULL Violation 1.) TFC 605.6 ELECTRICAL EXTENSION CORDS ARE NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING. THE EXTENSION CORDS CURRENTLY USED BEHIND THE ICE MACHINE AND ALSO ONE USED FOR POWERING A RADIO AND ADDING MACHINE IN THE SERVICE AREA MUST BE REMOVED.
05/08/2008 INSP - FULL Violation 2.) TFC 305.1 THE TRASH CAN IN THE BACK ROOM IS TOO CLOSE TO THE GAS WATER HEATER. THE FIRE CODE REQUIRES A SAFE CLEARANCE BETWEEN COMBUSTIBLE MATERIALS AND FLAME PRODUCING DEVICES.
05/08/2008 INSP - FULL Violation 3.) TFC 3003.5.3 THE CO2 CYLINDER IN THE BACK ROOM NEEDS TO BE SECURED TO PREVENT FALLING CAUSED BY CONTACT, VIBRATION OR SEISMIC ACTIVITY.
05/08/2008 INSP - FULL Violation 4.) TFC 904.5.1 WET-CHEMICAL EXTINGUISHING SYSTEMS SHALL BE INSPECTED AND TESTED FOR PROPER OPERATION AT 6 MO. INTERVALS.