Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/28/2008 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. |
| 05/07/2008 |
INSP - FULL |
|
Violation |
1.) TFC 510.1 APPROVED SIGN INDICATING "RISER ROOM" NEEDS TO BE FIXED ON DOOR FOR SPRINKLER SYSTEM CONTROL ROOM. |
| 05/07/2008 |
INSP - FULL |
|
Violation |
2.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT ABOVE EMPLOYEE ENTRANCE TO BACK ROOM IS NOT ILLUMINATING. |
| 05/07/2008 |
INSP - FULL |
|
Violation |
3.) TFC 605.6 ELECTRICAL JUNCTION BOX AT THE CEILING ABOVE LUGGAGE DEPT. NEEDS A COVER PLATE. |
| 05/07/2008 |
INSP - FULL |
|
Violation |
4.) TFC 605.6 ELECTRICAL JUNCTION BOX ABOVE DUCT WORK IN BACK ROOM BY EMPLOYEE ONLY ENTRANCE DOOR NEEDS A COVER PLATE. |
| 05/07/2008 |
INSP - FULL |
|
Violation |
5.) TFC 605.1 BROKEN ELECTRICAL OUTLET AND COVER PLATE NEAR FIRE EXTINGUISHER OUTSIDE EQUIPMENT REPAIR ROOM NEEDS TO BE REPLACED. |
| 05/07/2008 |
INSP - FULL |
|
Violation |
6.) TFC 903.3.3 SOLID WOOD STORAGE SHELVES ON THE NORTH WALL OF THE BACK ROOM IS OBSTRUCTING SPRINKLER COVERAGE FOR COMBUSTIBLE MATERIALS BELOW SHELVING. |
| 05/07/2008 |
INSP - FULL |
|
Violation |
7.) TFC 3404.3.5.4 GASOLINE, DIESEL CANS AND PAINT THINNER AND CHARCOAL LIGHTER FLUID NEED TO BE STORED SEPARATELY FROM COMBUSTIBLE MATERIALS IN SHED ON NORTH SIDE OF BUILDING. |