Case: T08FR01158

Parcel: 121120040


Addresses:

5421 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01158

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/28/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
05/07/2008 INSP - FULL Violation 1.) TFC 510.1 APPROVED SIGN INDICATING "RISER ROOM" NEEDS TO BE FIXED ON DOOR FOR SPRINKLER SYSTEM CONTROL ROOM.
05/07/2008 INSP - FULL Violation 2.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT ABOVE EMPLOYEE ENTRANCE TO BACK ROOM IS NOT ILLUMINATING.
05/07/2008 INSP - FULL Violation 3.) TFC 605.6 ELECTRICAL JUNCTION BOX AT THE CEILING ABOVE LUGGAGE DEPT. NEEDS A COVER PLATE.
05/07/2008 INSP - FULL Violation 4.) TFC 605.6 ELECTRICAL JUNCTION BOX ABOVE DUCT WORK IN BACK ROOM BY EMPLOYEE ONLY ENTRANCE DOOR NEEDS A COVER PLATE.
05/07/2008 INSP - FULL Violation 5.) TFC 605.1 BROKEN ELECTRICAL OUTLET AND COVER PLATE NEAR FIRE EXTINGUISHER OUTSIDE EQUIPMENT REPAIR ROOM NEEDS TO BE REPLACED.
05/07/2008 INSP - FULL Violation 6.) TFC 903.3.3 SOLID WOOD STORAGE SHELVES ON THE NORTH WALL OF THE BACK ROOM IS OBSTRUCTING SPRINKLER COVERAGE FOR COMBUSTIBLE MATERIALS BELOW SHELVING.
05/07/2008 INSP - FULL Violation 7.) TFC 3404.3.5.4 GASOLINE, DIESEL CANS AND PAINT THINNER AND CHARCOAL LIGHTER FLUID NEED TO BE STORED SEPARATELY FROM COMBUSTIBLE MATERIALS IN SHED ON NORTH SIDE OF BUILDING.