Case: T08FR01145

Parcel: 140290280


Addresses:

3321 E GLOBAL LP

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
06/27/2008 INSP - FULL Approved
05/07/2008 INSP - FULL Correction Required 901.6 Fire protection systems
1) Provide the south post indicator valve as to riser served
2) Provide the North spare head box, 1, 165 degree, concealed
sprinkler
3) Provide the South spare head box, 1, Viking B-2 sprinkler
4) B. A. T. room, plug one of the sprinkler heads that are closer
togeather than 6'. Maintain correct sprinkler spacing.
5) Replace escutcheons at the following places:
Old cafe store room
L & D
Rooms 122 & 139
Admin. office by copy machine
Service isle
East emergency exit by lockers