Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 04/30/2008 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
TFC 605.6 -Unapproved Conditions. Place an approved cover on the electrical outlet box located on the ground by the register. |
| 04/30/2008 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
TFC 605.1 -Abatement orf electrical hazards. Repair or replace the damaged cigarette machine electrical cord. |
| 04/30/2008 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
TFC 605.4 -Multiplug adapters. Remove the un-fused electrical adapters located in the register room. |
| 04/30/2008 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
TFC 605.4 -Multiplug adapters. Remove the un-fused cube adapter used to power the fridge in the south kitchen. |
| 04/30/2008 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
TFC 605.5 -Extension cords. Remove the orange extension cord located in the north kitchen. |