Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2008 | INSP - FULL | Approved | ||
| 04/29/2008 | INSP - FULL | Correction Required | The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). ___1. PROBLEM: Electrical panel missing breaker. Needs a blank. TUCSON FIRE CODE REFERENCE: 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. REQUIRED CORRECTION: Have blank installed in electrical panel. ___2. PROBLEM: Portable fire extinguisher in dish room has not been inspected/serviced since aug. of 2005. TUCSON FIRE CODE REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. REQUIRED CORRECTION: Have qualified individual service portable fire extinguisher. ___3. PROBLEM: Service records for hood suppression system not available on premises for inspection. TUCSON FIRE CODE REFERENCE: 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. REQUIRED CORRECTION: Keep copies of hood suppression system tests and maintenance records on premises for inspection. ___4. PROBLEM: Address not visible from street. TUCSON FIRE CODE REFERENCE: 505.1 Address numbers. (cot mod) New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. REQUIRED CORRECTION: Have address clearly displayed. The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated. Property Representative Signature: _________________________. Fire Inspector Signature: _________________________(791-4502). Reinspection Date: ___/___/___ or later. _X__Approved ___Not Approved |