Case: T08FR01028

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01028

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.05/29/08
04/24/2008 INSP - FULL Violation 1.) TFC 315.2.2 THE COMBUSTIBLE MATERIALS IN NORTHWEST E.D STAIRWELL NEED TO BE REMOVED.
04/24/2008 INSP - FULL Violation 2.) TFC 903.3.1 SPRINKLER HEAD ESCUTCHEON IS MISSING IN NORTHWEST E.D. STAIRWELL.
04/24/2008 INSP - FULL Violation 3.) TFC 703.1 REPAIR HOLE IN WALL NEAR DOOR IN RESIDENCE SLEEPING AREA ROOM 3.
04/24/2008 INSP - FULL Violation 4.) TFC 605.6 BROKEN OUTLET COVERS NEED TO BE REPAIRED/REPLACED IN ROOM 2-2 OF RESIDENCE SLEEPING AREA.
04/24/2008 INSP - FULL Violation 5.) TFC 3003.5.3 O2 BOTTLES IN AHCCCS OFFICE NEED TO BE SECURED TO PREVENT FALLING.
04/24/2008 INSP - FULL Violation 6.) TFC 903.3.1 SPRINKLER HEAD ESCUTCHEON IS MISSING IN NUCLEAR MEDS CHANGING ROOM.
04/24/2008 INSP - FULL Violation 7.) TFC 903.3.1 SPRINKLER HEAD ESCUTCHEON IS MISSING IN VASCULAR LAB HALLWAY OUTSIDE OF CONFERENCE ROOM.
04/24/2008 INSP - FULL Violation 8.) TFC 703.1 REPAIR HOLE IN WALL IN E/S CLOSET IN EAST HALLWAY OF VASCULAR LAB.
04/24/2008 INSP - FULL Violation 9.) TFC 1028.2 THE PAPER SHREDDER OUTSIDE ROOM 453 IN I.C.U. NEEDS TO BE REMOVED FROM REQUIRED EXIT ACCESS AREA.
04/24/2008 INSP - FULL Violation 10.) TFC 1011.1 AN EXIT SIGN IS REQUIRED AT THE SOUTH EXIT OF I.C.U. NEXT TO RECOVERY LOBBY.