Case: T08FR01013

Parcel: 13604328C

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01013

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2008 INSP - FULL Approved
05/30/2008 INSP - FULL Correction Required 5/30: During reinspection found additional violation: Front outside overhang has numerous open light sockets. One light bulb has a birds nest built around the bulb and socket. TFC REFERENCE: 605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. AND: 605.1 Abatement of electrical hazards. Identified electrical
hazards shall be abated.
REQUIRED CORRECTION: Replace missing light bulbs and clean birds nest out from around bulb.
04/22/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Fire extinguishers have no service tags on them.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.
REQUIRED CORRECTION: Either have fire extinguishers serviced or remove them.

___2. PROBLEM: Emergency lighting units not functioning properly.
TFC REFERENCE: 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
REQUIRED CORRECTION: Repair emergency lighting units.

___3. PROBLEM: Need additional exit sign in warehouse to point to exit.
TFC REFERENCE: 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit
shall not be allowed.
REQUIRED CORRECTION: Place exit sign indicating direction of exits in warehouse.

___4. PROBLEM: Vent in warehouse does not extend far enough through ceiling leaving insulation and space above ceiling exposed.
TFC REFERENCE: 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops,
shaft enclosures, partitions, smoke barriers, floors, fire-resistive
coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems) shall be
maintained. Such elements shall be properly repaired, restored
or replaced when damaged, altered, breached or penetrated.
Openings made therein for the passage of pipes, electrical conduit,
wires, ducts, air transfer openings and holes made for any
reason shall be protected with approved methods capable of
resisting the passage of smoke and fire.
REQUIRED CORRECTION: Extend vent tube through ceiling.

___5. PROBLEM: Weeds and vegetation growing around side of building.
TFC REFERENCE:304.1.2 Vegetation. Weeds, grass, vines or other growth that is capable of being ignited and endangering property,
shall be cut down and removed by the owner or occupant of
the premises.
REQUIRED CORRECTION: Cut and clear vegetation from around building.

___6. PROBLEM: Storage in front of electrical panel.
TFC REFERENCE: 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
REQUIRED CORRECTION: Keep area around electrical panel clear.

The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved