Case Number - T08FR01007
Inspection Description - INSP - AST/UST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2008 | INSP - AST/UST | Approved | All four tanks have the vents installed and the permit was issued | |
04/21/2008 | INSP - AST/UST | Correction Required | Dear Mr. Gill, The Tucson Fire Department has conducted a fire safety inspection at the above stated business on April 15, 2008. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about April 30, 2008. 3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent. - Normally closed vents shall be installed on the 4 oil tanks or the vents must discharge outside the building. |