Case: T08FR01007

Parcel: 13734001E


Addresses:

1698 W VALENCIA RD


Inspection Status: Approved

Inspection History: INSP - AST/UST

Case Number - T08FR01007

Inspection Description - INSP - AST/UST

Inspection Status - Approved

Date Description Inspector Results Comments
06/10/2008 INSP - AST/UST Approved All four tanks have the vents installed and the permit was issued
04/21/2008 INSP - AST/UST Correction Required Dear Mr. Gill,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on April 15, 2008. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about April 30, 2008.



3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent.
- Normally closed vents shall be installed on the 4 oil tanks or the vents must discharge outside the building.