Case: T08FR01004

Parcel: 121113250


Addresses:

4825 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR01004

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/21/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. 05/21/08
04/18/2008 INSP - FULL Violation 1.) TFC 605.4 CUBE TYPE ELECTRICAL PLUG ADAPTERS ARE NOT PERMITTED. ALL CUBE TYPE ADAPTERS NEED TO BE REPLACED WITH UL LISTED PLUG ADAPTERS WITH CIRCUIT BREAKER PROTECTION.
04/18/2008 INSP - FULL Violation 2.) TFC 605.6 ELECTRICAL OUTLETS AT THE TABLES FOR EACH STATION NEED TO BE MOUNTED IN APPROVED OUTLET BOXES.
04/18/2008 INSP - FULL Violation 3.) TFC 906.2 PORTABLE FIRE EXTINGUISHER NEEDS TO HAVE ANNUAL INSPECTION TAG AND MOUNTED IN A CONSPICUOUS PLACE.
04/18/2008 INSP - FULL Violation 4.) TFC 1008.1.8 THE DROP BAR LOCK ON THE REAR EXIT DOOR NEEDS TO BE REMOVED. THE METAL BRACKETS MUST ALSO BE REMOVED.