Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2008 | INSP - FULL | Approved | ||
| 04/15/2008 | INSP - FULL | Correction Required | The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). ___1. PROBLEM: Power cube used for coffe makers. TFC REFERENCE: 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. REQUIRED CORRECTION: Use approved GFI power strip to plug multiple appliances into. ___2. PROBLEM: Orange extension cord used under weiner cooker with power strip plugged into it. Power strips are only to be plugged into outlets. TFC REFERENCE: 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. REQUIRED CORRECTION: Extension cords are not to be used (see above) and power strips are to be plugged directly into outlets. The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated. Property Representative Signature: _________________________. Fire Inspector Signature: _________________________(791-4502). Reinspection Date: ___/___/___ or later. _X__Approved ___Not Approved |