Case: T08FR00938

Parcel: 13629003A


Addresses:

8251 E IRVINGTON RD


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR00938

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/13/2008 VIOL - FIRE PROTECTION SYSTEMS Approved Per Don Baker, System has been disabled by Ansul and gas has been shut off to appliances with gas line locked in the off position. Facility to notify proper permitting authorities prior to reactivating system.
04/14/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required The Tucson Fire Department has conducted a hood suppression system inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

PROBLEM: Suppression chemical is leaking out of right two nozzles and crystalizing.
TUCSON FIRE CODE REFERENCE: 901.6: " Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective." If nozzle tips are clogged it would adversly affect the hood systems ability to suppress a stove or grease fire.
REQUIRED CORRECTION: Have qualified individual repare leaking nozzle tips.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

___Approved

___Not Approved