Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/29/2008 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAE BEEN CORRECTED.05/29/08 |
| 04/10/2008 |
INSP - FULL |
|
Violation |
1.) TFC 1011.2 EXIT SIGNS FOR BOTH NORTH AND SOUTH DOORS OF WELL BABY NURSERY ARE NOT ILLUMINATED. |
| 04/10/2008 |
INSP - FULL |
|
Violation |
2.) TFC 903.3.1 SPRINKLER HEAD ESCUTCHEON IS MISSING IN ROOM 105 OF MOTHER/BABY PEDIATRIC WING. |
| 04/10/2008 |
INSP - FULL |
|
Violation |
3.) TFC 903.3.1 SPRINKLER HEAD ESCUTCHEON IS MISSING IN PLAY ROOM OF MOTHER/BABY PEDIATRIC WING. |
| 04/10/2008 |
INSP - FULL |
|
Violation |
4.) TFC 703.1 A WALL PENETRATION HOLE EXISTS IN SOILED UTILITY ROOM @ EAST HALLWAY NEXT TO ADMIN. E. D. OFFICES. |
| 04/10/2008 |
INSP - FULL |
|
Violation |
5.) TFC 703.1 A WALL PENETRATION HOLE EXISTS BY THE DOORWAY OF THE E. R. EDUCATION ROOM. |
| 04/10/2008 |
INSP - FULL |
|
Violation |
6.) TFC 703.1 A WALL PENETRATION HOLE EXISTS BEHIND THE ENTRANCE DOOR TO E.R. EDUCATION ROOM. |
| 04/10/2008 |
INSP - FULL |
|
Violation |
7.) TFC 703.1 OPENING AROUND VACUUM TUBE @ X-RAY VIEWING AREA IN HALLWAY ACROSS FROM TRAUMA 11 NEEDS TO BE SEALED. |
| 04/10/2008 |
INSP - FULL |
|
Violation |
8.) TFC 703.1 BROKEN LIGHT FIXTURE CREATING A CEILING PENETRATION IN TRIAGE AREA ABOVE WEIGHT SCALES NEEDS TO BE REPAIRED. |
| 04/10/2008 |
INSP - FULL |
|
Violation |
9.) TFC 703.1 BROKEN LIGHT FIXTURE CREATING A CEILING PENETRATION OUTSIDE OF E. D. RECEPTION AREA NEEDS TO BE REPAIRED. |
| 04/10/2008 |
INSP - FULL |
|
Violation |
10.) TFC 703.1 WATER DAMAGE CREATION A PENETRATION HOLE @ DUCT WORK AND ABOVE IN THE CEILING OUTSIDE OF EXAM ROOM 4 OF E. D. |