Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Case: T08FR00892

Parcel: 12507172A


Addresses:

2501 E 6TH ST

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
04/09/2008 VIOL - MEANS OF EGRESS Violation 2006 IFC 1008.1.9
REMOVE DBL KEYED LOCK ON REAR EXIT DOOR AND REPAIR THE PANIC HARDWARE. THE PANIC HARDWARE IS THE ONLY LOCKING MECHANISM ALLOWED.
04/09/2008 VIOL - MEANS OF EGRESS Violation 2006 IFC 1027.3
REPAIR EXIT SIGN ABOVE REAR EXIT DOOR.
04/09/2008 VIOL - MEANS OF EGRESS Violation 2006 IFC 1027.5
REPAIR EMERGENCY LIGHT AT REAR EXIT