Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T08FR00892
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.4 REMOVE THE MULTIPLUG ADAPTER ABOVE THE BUD LIGHT SIGN AND REPLACE WITH A FUSED POWER STRIP REMOVE MULTIPLUG ADAPTER AT THE SIDE STATION BY TV AND USE A FUSED POWER STRIP |
|
04/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.6 REMOVE EXTENSION CORD AT SIDE STATION BY TV. |
|
04/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.5 REMOVE EXTENSION CORD BY TIME CLOCK REMOVE EXTENSION CORD ON FLOOR BY CHARBROILER GRILL |
|
04/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.1 REPLACE MISSING COVER ON OUTLET BY MEAT SLICER |