Case: T08FR00859

Parcel: 12112062C


Addresses:

5101 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
04/16/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
04/08/2008 INSP - FULL Violation 1.) TFC 906.2 PORTABLE FIRE EXTINGUISHERS LOCATED THROUGHOUT THE BUILDING SHALL BE INSPECTED AND TESTED ANNUALLY.
04/08/2008 INSP - FULL Violation 2.) TFC 906.2 THE "K" TYPE EXTINGUISHER NEEDS TO BE INSPECTED AND TAGGED WITH AND UP TO DATE TAG.
04/08/2008 INSP - FULL Violation 3.) TFC 605.6 THE OPEN WIRE SPLICES NEAR THE CEILING LIGHT FIXTURE IN THE STOCK ROOM NEEDS TO BE ENCLOSED.
04/08/2008 INSP - FULL Violation 4.) TFC 605.4 THE ELECTRICAL PLUG ADAPTOR ABOVE THE WINDOW ON THE SOUTH WALL NEAR THE SOUTH EAST CORNER OF THE BUILDING NEEDS TO BE REPLACED WITH A FUSED, UL LISTED PLUG ADAPTOR.
04/08/2008 INSP - FULL Violation 5.) TFC 903.5 THE SPRINKLER HEADS IN THE KITCHEN MUST BE CLEANED AND FREE FROM GREASE IN ORDER TO OPERATE PROPERLY.
04/08/2008 INSP - FULL Violation 6.) TFC 510.1 THE CLOSET IN THE BACK ROOM NEEDS A SIGN ON THE DOOR INDICATING SPRINKLER RISER.
04/08/2008 INSP - FULL Violation 7.) TFC 904.5.1 COMMERCIAL KITCHEN HOOD EXTINGUISHING SYSTEM SHALL BE INSPECTED AND TESTED AT 6 MO. INTERVALS. THE HOOD SYSTEM IN PAST DUE FOR INSPECTION.
04/08/2008 INSP - FULL Violation 8.) TFC 904.11 COMMERCIAL KITCHEN AUTOMATIC FIRE-EXTINGUISHING SYSTEMS SHALL BE TESTED AND BE IN ACCORDANCE WITH UL 300.