Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR00842
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2008 | INSP - FULL | Approved | All corrected. | |
04/08/2008 | INSP - FULL | Correction Required | 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. ___Provide copy of annual fire sprinkler and alarm report. |
|
04/08/2008 | INSP - FULL | Correction Required | 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. ___Label Riser Rooms with signage and indicating the appropriate address controlled by each riser. |
|
04/07/2008 | INSP - FULL | Correction Required | 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. ___ Provide minimum 18" clearance from 5" cap to finished ground level. |
|
04/02/2008 | INSP - FULL | Correction Required | 506.2 Key box maintenance. The operator of the building shall immediately notify the fire code official and provide the new key when a lock is changed or rekeyed. The key to such lock shall be secured in the key box. ___Provide keys for riser rooms in knox box. |