Case: T08FR00840

Parcel: 128010190

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00840

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/08/2008 INSP - FULL Approved All corrected.
04/02/2008 INSP - FULL Correction Required 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.
___Keep area in front of electric panels clear.
04/02/2008 INSP - FULL Correction Required 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
___Multi-plug adapters are not to be plugged into other multi-plug adapters.
04/02/2008 INSP - FULL Correction Required 1021.2 Width. The width of exit passageways shall be determined as specified in Section 1005.1 but such width shall not be less than 44 inches (1118 mm), except that exit passageways serving an occupant load of less than 50 shall not be less than 36 inches (914 mm) in width.
___Keep rear exit access clear.
04/02/2008 INSP - FULL Correction Required 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions.
___Hang extinguisher in employee break area.