Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR00809
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2008 | INSP - FULL | Approved | Sprinkler protection added in high dollar lock up room and over cart storage. All approved. | |
04/02/2008 | INSP - FULL | Correction Required | 315.3.1 Storage beneath overhead projections from buildings. Combustible materials stored or displayed outside of buildings that are protected by automatic sprinklers shall not be stored or displayed under nonsprinklered eaves canopies or other projections or overhangs. ___Carts under overhang need to be moved. |
|
04/01/2008 | INSP - FULL | Correction Required | 903.3.1.1 NFPA 13 sprinkler systems. Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13 except as provided in Section 903.3.1.1.1. ___Install sprinkler head in high-dollar lock-up room. |