Case: T08FR00809

Parcel: 128010190


Addresses:

6228 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00809

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2008 INSP - FULL Approved Sprinkler protection added in high dollar lock up room and over cart storage. All approved.
04/02/2008 INSP - FULL Correction Required 315.3.1 Storage beneath overhead projections from buildings. Combustible materials stored or displayed outside of buildings that are protected by automatic sprinklers shall not be stored or displayed under nonsprinklered eaves canopies or other projections or overhangs.
___Carts under overhang need to be moved.
04/01/2008 INSP - FULL Correction Required 903.3.1.1 NFPA 13 sprinkler systems. Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13 except as provided in Section 903.3.1.1.1.
___Install sprinkler head in high-dollar lock-up room.