Case: T08FR00800

Parcel: 13409018C


Addresses:

8510 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00800

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/27/2008 INSP - FULL Approved
03/27/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Orange extension cord leading to power strip on band stand and extension cord powering T.V. over bar.
TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
REQUIRED CORRECTION: Appliances must be plugged directly into an electrical outlet or into an approved GFI power strip.

___2. PROBLEM: Exit off patio has slide bolt securing both doors.
TFC REFERENCE: 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
REQUIRED CORRECTION: Upper and lower slide bolts on the one door are acceptable, but middle slide bolt must be removed.

___3. PROBLEM: Open light socket in men's room and outside of men's room.
TFC REFERENCE: 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
REQUIRED CORRECTION: Put proper light bulbs in sockets or socket covers.

___4. PROBLEM: Use of power cube in office and to blender behind bar.
TFC REFERENCE: 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
REQUIRED CORRECTION: Remove power cubes and use power strip or plug appliance directly into outlet.

___5. PROBLEM: Unsecured gas canister by office.
TFC REFERENCE: 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity.
REQUIRED CORRECTION: Properly secure gas canister by office.

___6. PROBLEM: Portable fire extinguisher by office is in empty range and was last serviced 12/03. Portable fire extinguisher behind bar was last serviced 12/03. They are required to be serviced every year.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.
REQUIRED CORRECTION: Have portable fire extinguishers serviced by qualified professional.

___7. PROBLEM: electrical cord behind liquor rack spliced together then leading through wall to ?
TFC REFERENCE: 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. AND: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls...
REQUIRED CORRECTION: Remove spliced electrical cord and do not pass cords through walls.

___8. PROBLEM: Certificate of Occupancy not posted or available for viewing.
TFC REFERENCE: 105.3.5 Posting the permit. Issued permits shall be kept on the premises designated therein at all times and shall be
readily available for inspection by the fire code official.
REQUIRED CORRECTION: Certificate of Occupancy shall be available on the premises for fire code official to inspect.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved