Case: T08FR00796

Parcel: 10714257C


Addresses:

100 W GRANT RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR00796

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
03/26/2008 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.5 Unlatching.
The unlatching of any door or leaf shall not require more than one operation.

1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____ Remove all self made brackets from rear egress door

1011.4 Internally illuminated exit signs.
Internally illuminated exit signs shall be listed and labeled and shall be installed in accordance with the manufacturer's instructions and Section 2702 of the International Building Code. Exit signs shall be illuminated at all times.

____ Fix all exit signs


________________________________________________
(Joseph P. Longo, Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report.
(Building Representative)

______________________________
(Captain)

Full inspection done by Inspector Joseph P. Longo
Re-inspection scheduled on or after __4_/_8__/_08__
Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions.
Thank you.

Re-inspection passed: