Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T08FR00792

Parcel: 12415016B


Addresses:

810 E 17TH ST

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/26/2008 INSP - FULL Violation 407.2 Material Safety Data Sheets. Material Safety Data
Sheets (MSDS) for all hazardous materials shall be readily
available on the premises.
407.3 Identification. Individual containers of hazardous materials,
cartons or packages shall be marked or labeled in accordance
with applicable federal regulations. Buildings, rooms
and spaces containing hazardous materials shall be identified
by hazard warning signs in accordance with Section 2703.5.
407.4 Training. Persons responsible for the operation of areas
in which hazardous materials are stored, dispensed, handled or
used shall be familiar with the chemical nature of the materials
and the appropriate mitigating actions necessary in the event of
a fire, leak or spill. Responsible persons shall be designated and
trained to be liaison personnel for the Fire Department. These
persons shall aid the Fire Department in preplanning emergency
responses and identification of the locations where hazardous
materials are located, and shall have access to Material
Safety Data Sheets and be knowledgeable in the site emergency
response procedures.
Every employee needs to know how to find M.S.D.S. for emergency response.
03/26/2008 INSP - FULL Violation 505.1 Address numbers. New and existing buildings shall
have approved address numbers, building numbers or approved
building identification placed in a position that is plainly legible
and visible from the street or road fronting the property.
These numbers shall contrast with their background. Address
numbers shall be Arabic numerals or alphabet letters.
See handout for proper size.
03/26/2008 INSP - FULL Violation 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor cover-ings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.
605.5.1 Power supply. Extension cords shall be plugged directly
into an approved receptacle, power tap or multiplug
adapter and, except for approved multiplug extension cords,
shall serve only one portable appliance.
Do not use extension cords for perminant wiring.
03/26/2008 INSP - FULL Violation 703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, fire stops,
shaft enclosures, partitions and floors) shall be maintained.
Such elements shall be properly repaired, restored or replaced
when damaged, altered, breached or penetrated. Openings
made therein for the passage of pipes, electrical conduit, wires,
ducts, air transfer openings, and holes made for any reason
shall be protected with approved methods capable of resisting
the passage of smoke and fire. Openings through fire-resistance-
rated assemblies shall be protected by self-closing or automatic-
closing doors of approved construction meeting the
fire protection requirements for the assembly.
703.1.1 Fireblocking and draftstopping. Required
fireblocking and draftstopping in combustible concealed
spaces shall be maintained to provide continuity and integrity
of the construction.
703.1.2 Smoke barriers. Required smoke barrier partitions
shall be maintained to prevent the passage of smoke and all
openings protected with approved smoke barrier doors or
leakage-rated (smoke) dampers.
703.2 Opening protectives. Opening protectives shall be
maintained in an operative condition in accordance with NFPA
80. Fire doors and smoke barrier doors shall not be blocked or
obstructed or otherwise made inoperable. Fusible links shall be
replaced promptly whenever fused or damaged. Fire door assemblies
shall not be modified.
Close all holes in sprinklered rooms.
03/26/2008 INSP - FULL Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an operative
condition at all times, and shall be replaced or repaired
where defective. Nonrequired fire protection systems and
equipment shall be inspected, tested and maintained or removed.
901.6.1 Standards. Fire protection systems shall be inspected,
tested and maintained in accordance with the referenced
standards listed in Table 901.6.1.
Yearly test required for riser. Riser needs to be taged.
03/26/2008 INSP - FULL Violation 1011.1 Where required. Exits and exit access doors shall be
marked by an approved exit sign readily visible from any direction
of egress travel. Access to exits shall be marked by readily
visible exit signs in cases where the exit or the path of egress
travel is not immediately visible to the occupants. Exit sign
placement shall be such that no point in an exit access corridoris more than 100 feet (30 480 mm) or the listed viewing distance
for the sign, whichever is less, from the nearest visible
exit sign.
Post EXIT signs no more than every 100 Ft. in direction of travel.