Case: T08FR00782

Parcel: 12901018F


Addresses:

2222 E BROADWAY BL


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T08FR00782

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
03/24/2008 INSP - FULL Violation 305.1 Clearance from ignition sources. Clearance between
ignition sources, such as light fixtures, heaters and flame-producing
devices, and combustible materials shall be maintained
in an approved manner.
Remove all combustables from Hot Water heater area.
03/24/2008 INSP - FULL Violation 315.2 Storage in buildings. Storage of combustible materials
in buildings shall be orderly. Storage shall be separated from
heaters or heating devices by distance or shielding so that ignition
cannot occur.
315.2.1 Ceiling clearance. Storage shall be maintained 2
feet (610 mm) or more below the ceiling in nonsprinklered
areas of buildings or a minimum of 18 inches (457 mm) below
sprinkler head deflectors in sprinklered areas of buildings.
keep boxes 2 feet below celing.
03/24/2008 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
Do not block electrical panels.