Case: T08FR00774

Parcel: 13409002C


Addresses:

8358 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00774

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/09/2008 INSP - FULL Approved
03/20/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Power strips need to be secured.
TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.
REQUIRED CORRECTION: Secure power strips so that weight of plugs are not holding it.

___2. PROBLEM: Unapproved yellow extension cord used in back for light and orange extension cord used up front.
TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
REQUIRED CORRECTION: Plug appliances into outlet or into approved power strip with GFI.

___3. PROBLEM: Ceiling tiles missing up front.
TFC REFERENCE: 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops,
shaft enclosures, partitions, smoke barriers, floors, fire-resistive
coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems) shall be
maintained. Such elements shall be properly repaired, restored
or replaced when damaged, altered, breached or penetrated.
Openings made therein for the passage of pipes, electrical conduit,
wires, ducts, air transfer openings and holes made for any
reason shall be protected with approved methods capable of
resisting the passage of smoke and fire.
REQUIRED CORRECTION: Replace ceiling tiles upon completion of repairing leak.

___4. PROBLEM: Certificate of Occupancy not posted.
TFC REFERENCE: 105.3.5 Posting the permit. Issued permits shall be kept on the premises designated therein at all times and shall be
readily available for inspection by the fire code official.
REQUIRED CORRECTION: C of O shall be posted for the fire official to observe.

___5.PROBLEM: Exit signs not illumined.
TFC REFERENCE: 1011.2 Illumination. Exit signs shall be internally or externally illuminated.
REQUIRED CORRECTION: Repair exit signs.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved