Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/09/2008 |
INSP - FULL |
|
Approved |
ALL TFC VIOLATIONS HAVE BEEN CORREDTED. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
1.) TFC 1011.5.3 EXIT SIGN ABOVE EAST MAIN DOOR NEEDS TO BE INTERNALLY OR EXTERNALLY ILLUMINATED. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
2.) TFC 1006.3 EMERGENCY ILLUMINATION UNIT ABOVE CASHIER'S COUNTER IS NOT OPERATING. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
3.) TFC 605.6 ELECTRICAL JUNCTION BOX ON WEST WALL IN DISPLAY AREA NEEDS A COVER PLATE INSTALLED. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
4.) TFC 703.1.1 BROKEN CEILING TILE IN WEST TUNNEL NEEDS TO BE REPLACED. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
5.) TFC 1006.3 EMERGENCY ILLUMINATION UNIT IN THE NORTHWEST CORNER OF DISPLAY AREA IS NOT ILLUMINATING. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
6.) TFC 1011.5.3 EXIT SIGN ABOVE DOOR AT THE NORTH END OF THE WEST TUNNEL NEEDS TO BE INTERNALLY OR EXTERNALLY ILLUMINATED. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
7.) TFC 605.6 ELECTRICAL JUNCTION BOX ON WALL IN MARKETING DEPT. NEAR CEILING NEEDS TO HAVE A COVER PLATE INSTALLED. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
8.) TFC 315.2.2 COMBUSTIBLE MATERIALS STORED UNDER DAVE BAKER'S OFFICE NEEDS TO BE REMOVED TO PROVIDE FOR EXIT ACCES IN CASE OF A FIRE. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
9.) TFC 1011.1 READILY VISIBLE EXIT SIGNS NEED TO INSTALLED ON OR ABOVE BOTH REAR EXIT DOORS. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
10.) TFC 605.3 MISC. STORAGE NEEDS TO BE REMOVED TO MAINTAIN ACCESS TO BOTH ELECTRICAL BREAKER PANELS IN BACK ROOM. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
11.) TFC 703.1.1 REPAIR HOLE IN CEILING ABOVE SHELVES IN SLEEPING BAG BACK STOCK AREA IN BACK ROOM TO MAINTAIN REQUIRED FIRE BLOCKING AND DRAFT STOPPING. |
| 03/19/2008 |
INSP - FULL |
|
Violation |
12.) TFC1006.3 EMERGENCY ILLUMINATION UNIT AT THE NORTH END OF THE EAST TUNNEL IN NOT OPERATING. |