Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T08FR00764
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
| 03/18/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Blocked electrical panel: IFC 2006 with modifications 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ______Clear area in front of electrical panel in an approved manner. |
|
| 03/18/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Extension cords: IFC2006 [TFC with modifications] / 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____Replace with approved power strips. Re-inspection date scheduled on or after April 2, 2008. If you have any questions or concerns please call Inspector Cobb at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department __________________________I have received a copy of this inspection report. Building Representative _____________________________________________ Captain |