Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T08FR00763
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Violation
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/18/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Extinguishers not mounted: IFC2006 [TFC with modifications] / 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ______ Mount extinguishers in an approved manner. Re-inspection date scheduled on or after April 2, 2008. If you have any questions or concerns please call Inspector Cobb at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department __________________________I have received a copy of this inspection report. Building Representative _____________________________________________ Captain |