Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T08FR00763

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
03/18/2008 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:

IFC2006 [TFC with modifications] / 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____Replace with approved power strip.
03/18/2008 VIOL - BUILDING SVCS & SYSTEMS Violation Open wire box:

IFC2006 [TFC with modifications] / 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

______Cover wires in an approved manner [outlet cover over counter].
03/18/2008 VIOL - BUILDING SVCS & SYSTEMS Violation Temp light used for permanant purpose;

IFC2006 [TFC with modifications] / 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

______ Remove light from over counter.