Case: T08FR00739

Parcel: 127022550


Addresses:

5252 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
04/16/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
03/17/2008 INSP - FULL Violation 1.) TFC 605.3 FLAMMABLE AND COMBUSTIBLE LIQUIDS NEED TO BE REMOVED FROM CLOSE PROXIMITY TO THE ELECTRICAL BREAKER PANEL ON THE SOUTH WALL OF PROCESSING AREA AND STORED IN AN APPROVE CABINET.
03/17/2008 INSP - FULL Violation 2.) TFC 605.3 ALL MISC. STORAGE AROUND THE ELECTRICAL BREAKER PANEL ON THE SOUTH WALL OF THE PROCESSING AREA NEEDS TO BE REMOVED TO MAINTAIN A MINIMUM OF 30" CLEARANCE IN FRONT OF THE PANEL.
03/17/2008 INSP - FULL Violation 3.) TFC 605.3 THE STORAGE AROUND THE ELECTRICAL BREAKER PANEL ON THE EAST WALL OF THE PROCESSING AREA NEEDS TO BE REMOVED TO MAINTAIN A MINIMUN OF 30" CLEARANCE IN FRONT OF THE PANEL.
03/17/2008 INSP - FULL Violation 4.) TFC 605.6 THE OUTLET ON THE NORTH WALL OF THE DUNGEON NEEDS A COVER PLATE INSTALLED.
03/17/2008 INSP - FULL Violation 5.) TFC 703.1.1 OPENINGS IN THE CEILING IN THE DUNGEON NEED TO BE PROPERLY SEALED TO MAINTAIN FIRE BLOCKING AND DRAFT STOPPING.
03/17/2008 INSP - FULL Violation 6.) TFC 605.6 ELECTRICAL SWITCH BOX IN PROCESSING AREA NEAR THE ENTRANCE TO THE DUNGEON NEEDS TO HAVE THE COVER PLATE SECURED TO THE BOX.
03/17/2008 INSP - FULL Violation 7.) TFC 703.1.1 MISSING CEILING TILE IN THE BACK ROOM NEED TO BE REPLACED TO MAINTAIN FIRE BLOCKING AND DRAFT STOPPING.
03/17/2008 INSP - FULL Violation 8.) TFC 605.1 EXTENSION CORD LOCATED ON THE WEST WALL OF THE BACK ROOM NEEDS TO BE REMOVED FROM SERVICE. NO OPEN SPLICES ARE ALLOWABLE.
03/17/2008 INSP - FULL Violation 9.) TFC605.5 EXTENSION CORDS USED FOR LIGHTING FIXTURES OVER THE DRESSING ROOMS NEED TO BE REPLACED WITH PERMANENT WIRING. EXTENSION CORDS SHALL NOT BE A SUBSTITUTE FOR PERMANENT WIRING.
03/17/2008 INSP - FULL Violation 10.) TFC 703.1.1 MISSING CEILING TILE IN SHOW ROOM AREA NEED TO BE REPLACED TO MAINTAIN FIRE BLOCKING AND DRAFT STOPPING.